45030A Printed in Canada 07-03-2012 CONVENTIONAL WOOD STOVES OWNER’S MANUAL NORDIC AND SAWMAN STOVE BUILDER INTERNATIONAL INC. 250
10 Graphic 1 A- Minimum clearance required between the appliance and an unshielded combustible ceiling. B- 20 in. (500 mm) minimum; C- 1 in. (
11 Graphic 2 A- 1 in. (25 mm) minimum; 1- Combustible wall; 2- Non-combustible spacers; 3- 0.024’’ (0.61mm) sheet metal. Graphic 3 A- 1 in. (25
12 Graphic 5 A- 1 in. (25 mm) minimum; 1- Combustible wall; 2- Non-combustible spacers; 3- Brick. Graphique 6 A- 1 in. (25 mm) minimum; 1- Com
13 CHIMNEY Your wood stove may be hooked up with a prefabricated or masonry chimney. If you are using a prefab chimney, it must comply with S-629 st
14 Stove pipe An adequate number of stove pipe sections. A 90o elbow 1- Start by positioning your stove where you would like it to go, taking
15 4- Then, from outside the building, slide a short chimney length (attached to the tee) through the wall thimble. The chimney must extend at least
16 7- Authorities require that the chimney extend not less than 3 feet above the highest point where it passes through the roof of a building and not
17 Stove pipe Suitable lengths of stove pipe 1- Place your stove where you would like it located and use a plumb line to mark the ceiling direc
18 4- Once the support is secure, you can begin to assemble the chimney by lowering the first section into the support. Make sure that the male coup
19 8- Next, slide the storm collar down the chimney until it contacts the flashing. Tighten the nut and bolt and seal the collar to the chimney with
2 TABLE OF CONTENTS INTRODUCTION ...
20 FIGURE 2.3 (A) Connecting Sections FIGURE 2.3 (B) Minimum Slope The assembly should be as short and direct as possible between the stove
21 DRAFT Your Drolet stove’s performance will be optimized if it is installed with a chimney (flue) system that provides an adequate draft. The draf
22 BAFFLE BRICK INSTALLATION (SAWMAN STOVE ONLY) - The Sawman C-Cast baffle is shipped with the stove. However, in order to avoid shipping damages,
23 OPERATING YOUR DROLET WOOD STOVE FUEL Your stove was designed to burn wood only. No other type of fuel should be used. Waste and other flammable
24 Smaller pieces of wood will dry faster. All logs exceeding 6" (152 mm) should be split. The wood should be stored in a place where the grass
25 HEATING Once you have obtained a good bed of embers you should reload the unit. In order to do so, open the air control completely for a few seco
26 MAINTENANCE OF THE HEATING SYSTEM MAINTENANCE OF THE STOVE Our wood stoves are designed so that they will require little maintenance: - It is w
27 MAINTENANCE OF THE CHIMNEY Whether you have a prefab or masonry chimney, you must conduct a visual inspection at least once a month in order to be
28 DROLET LIMITED LIFETIME WARRANTY The warranty of the manufacturer extends only to the original consumer purchaser and is not transferable. This wa
3 INTRODUCTION THE DROLET WOOD STOVE MANUAL SBI INC., one of the most important wood stove and fireplace manufacturers in North America, congratulat
4 ASSEMBLING THE STOVE Note: This section applies to Nordic model only. 1- Mount the 4 legs using 2 screws per leg. 2- Mount the ash lip with two
5 INSTALLING THE FIREBRICKS Note: This section applies to Nordic model only.
6 INSTALLATION OF YOUR DROLET WOOD STOVE POSITIONING THE STOVE It is very important to position the wood stove as close as possible to the chimney,
7 FIGURE 1.3 Clearances to combustible materials and floor protection
8 Floor protector If the stove is to be installed on top of a combustible floor, it must be guarded by a non combustible material as shown on figure
9 TYPE OF PROTECTION Reducing Clearances With Shielding Sides and Rear/Back Top Sheet metal, a minimum of 0,024" (0,61mm) spaced out at least 1&
Comments to this Manuals